Sound data, Method of sound measurement, Condensers – Airedale Air Cooled Condensers R407C User Manual

Page 12: Measurement of sound data, Semi hemispherical, Standard condenser fan – horizontal, Standard condenser fan – vertical

Advertising
background image

C11-45 / CS50 - 105

CONDENSERS

12

Condensers

Installation and Maintenance Manual: 6259642 V1.2.0 02/2013

Sound Data

METHOD OF SOUND MEASUREMENT

Measurement of Sound
Data

All sound data quoted has been measured in the third-octave band limited values, using
a Real Time Analyser calibrated sound intensity meter in accordance with
BS EN ISO9614 Part 1 : 1995.

All Sound Power Levels quoted are calculated from measured sound intensity according
BS EN ISO9614 Part 1 : 1995.

Semi Hemispherical

Sound Pressure Levels are calculated from sound power using the semi-hemispherical
method where the noise source is in junction with 2 boundaries i.e. the floor and 1 wall.

SOUND DATA

Standard Condenser Fan

– Horizontal

Sound
Measurement

Overall
dB(A)

Frequency (Hz) dB

63

125

250

500

1000

2000

4000

8000

C11HI-H

Power

dB(A)

67

56

58

63

64

63

61

55

47

Pressure

@ 10m

39

28

30

35

36

35

33

27

19

C15HI-H

Power

dB(A)

70

59

61

66

67

66

64

58

50

Pressure

@ 10m

42

31

33

38

39

38

36

30

22

C20HI-H

Power

dB(A)

79

78

87

76

73

74

70

62

55

Pressure

@ 10m

51

50

59

48

45

46

42

34

27

C25HI-H

Power

dB(A)

79

78

87

76

73

74

70

62

55

Pressure

@ 10m

51

50

59

48

45

46

42

34

27

C35HI-H

Power

dB(A)

79

78

87

76

73

74

70

62

55

Pressure

@ 10m

51

50

59

48

45

46

42

34

27

C45HI-H

Power

dB(A)

82

81

90

79

76

77

73

65

61

Pressure

@ 10m

54

53

62

51

48

49

45

37

33

CS50H

Power

dB(A)

81

84

89

77

77

76

73

66

65

Pressure

@ 10m

53

56

61

49

49

48

45

38

37

CS65H

Power

dB(A)

81

84

89

77

77

76

73

66

65

Pressure

@ 10m

53

56

61

49

49

48

45

38

37

CS80H

Power

dB(A)

83

80

89

80

77

79

75

68

67

Pressure

@ 10m

55

52

61

52

49

51

47

40

39

CS105H

Power

dB(A)

83

80

89

80

77

79

75

68

67

Pressure

@ 10m

55

52

61

52

49

51

47

40

39

Standard Condenser Fan

– Vertical

Sound
Measurement

Overall
dB(A)

Frequency (Hz) dB

63

125

250

500

1000

2000

4000

8000

C11HI-V

Power

dB(A)

68

53

61

63

64

64

62

56

48

Pressure

@ 10m

40

25

33

35

36

36

34

28

20

C15HI-V

Power

dB(A)

71

56

64

66

67

67

65

59

51

Pressure

@ 10m

43

28

36

38

39

39

37

31

23

C20HI-V

Power

dB(A)

80

75

92

76

73

75

71

63

56

Pressure

@ 10m

52

47

64

48

45

47

43

35

28

C25HI-V

Power

dB(A)

80

75

92

76

73

75

71

63

56

Pressure

@ 10m

52

47

64

48

45

47

43

35

28

C35HI-V

Power

dB(A)

80

75

92

76

73

75

71

63

56

Pressure

@ 10m

52

47

64

48

45

47

43

35

28

C45HI-V

Power

dB(A)

83

78

95

79

76

78

74

66

62

Pressure

@ 10m

55

50

67

51

48

50

46

38

34

CS50V

Power

dB(A)

83

81

93

77

77

78

74

68

67

Pressure

@ 10m

55

53

65

49

49

50

46

40

39

CS65V

Power

dB(A)

83

81

93

77

77

78

74

68

67

Pressure

@ 10m

55

53

65

49

49

50

46

40

39

CS80V

Power

dB(A)

84

76

93

80

78

81

76

70

69

Pressure

@ 10m

56

48

65

52

50

53

48

42

41

CS105V

Power

dB(A)

84

76

93

80

78

81

76

70

69

Pressure

@ 10m

56

48

65

52

50

53

48

42

41

1

Figures quoted using standard condenser fan(s) running at full speed under normal operating conditions.

Advertising