Dimensional & installation data, Dimensions / masses / positioning - horizontal, Condensers – Airedale Air Cooled Condensers R407C User Manual

Page 13: Standard condenser fan (mm) (c11 shown)

Advertising
background image

CONDENSERS

C11 - 45 / CS50 - 105

Condensers

13

Installation and Maintenance Manual: 6259642 V1.2.0 10/2013

Dimensional & Installation Data

DIMENSIONS / MASSES / POSITIONING - HORIZONTAL

Standard Condenser Fan (mm) (C11 Shown)

C

G

A

D

(3)

(4a)

F

B

(4b)

500

(2)

500

(2)

500

(2)

1800

(2)

(1)

(1)

(1)

(5)

E

Optional Short Case Axial Fan (mm) (SCAF) (C45 Shown)

DIMENSIONS (mm)

MASS (kg)

Standard Fan

Optional SCAF

Standard

Fan

Optional

SCAF

A

B

C

D

E

F

G

G1(6)

B

F

C11HI-H

648

550

1275

455

530

550

1118

N/A

675

640

51

61

C15HI-H

648

550

1275

455

530

550

1118

N/A

675

640

63

73

C20HI-H

848

645

1100

455

530

550

944

N/A

735

640

58

70

C25HI-H

848

645

1100

455

530

550

944

N/A

735

640

65

77

C35HI-H

1048

645

1650

455

530

550

1494

N/A

711

640

97

109

C45HI-H

1048

645

1650

455

530

550

1494

N/A

711

640

110

134

(1)

Airflow

(2)

Minimum clearances in mm

(3)

8mm fixing points

(4)

Service connections to left hand side of the unit: a = Liquid Outlet, b = Discharge Gas Inlet

(5)

Mains Electric Isolator, (CS50

– C105 located behind open side panel)

(6)

Additional support to sizes C80

– CS105

(7)

4 lifting eye bolts to unit top, sizes CS50

– CS105

(8)

Optional Short Case Axial Fan with integral duct fixing holes

Advertising