Heat pump heating fixed capacities, Condensing units blucube, Condensing units – Airedale BluCube 10-48kW User Manual

Page 43

Advertising
background image







Condensing Units

BluCube

Condensing Units

43

Installation and Maintenance Manual 7222094: 11/2013

Heat Pump Heating Fixed Capacities

Winter Ambient (°C)

-5

0

5

10

15

Unit

Cond

Temp

(°C)

Output

(kW)

Input

(kW)

Output

(kW)

Input

(kW)

Output

(kW)

Input

(kW)

Output

(kW)

Input

(kW)

Output

(kW)

Input

(kW)

CUR092V16-1HP-0

40

11.2

4.2

12.5

4.2

13.9

4.2

15.4

4.2

17.1

4.2

45

11.1

4.6

12.4

4.6

13.8

4.6

15.3

4.6

16.9

4.6

50

N/A

N/A

12.3

5.1

13.7

5.1

15.2

5.1

16.7

5.1

55

N/A

N/A

N/A

N/A

13.6

5.7

15.1

5.7

16.6

5.6

CUR092V20-1HP-0

40

16.0

6.0

17.8

6.0

19.7

6.0

21.7

6.0

23.9

6.0

45

15.8

6.5

17.7

6.6

19.6

6.6

21.5

6.6

23.7

6.6

50

N/A

N/A

17.4

7.1

19.4

7.2

21.3

7.2

23.4

7.2

55

N/A

N/A

N/A

N/A

N/A

N/A

21.1

7.8

23.1

7.8

CUR092V25-1HP-0

40

19.7

7.5

21.8

7.5

24.2

7.6

26.7

7.6

29.4

7.7

45

19.9

8.2

22.0

8.3

24.2

8.3

26.6

8.4

29.3

8.4

50

N/A

N/A

N/A

N/A

24.2

9.1

26.6

9.2

29.1

9.3

55

N/A

N/A

N/A

N/A

N/A

N/A

26.5

10.2

28.9

10.2

CUR092V29-1HP-0

40

21.6

8.2

24.0

8.3

26.5

8.3

29.2

8.4

32.0

8.5

45

21.7

9.0

24.0

9.1

26.4

9.2

29.0

9.3

31.8

9.3

50

N/A

N/A

N/A

N/A

26.4

10.2

28.9

10.2

31.6

10.3

55

N/A

N/A

N/A

N/A

N/A

N/A

28.8

11.3

31.4

11.4

CUR122V35-1HP-0

40

28.9

13.0

32.0

13.0

35.6

13.0

39.2

13.0

43.2

13.1

45

29.1

14.2

32.1

14.2

35.5

14.2

39.0

14.2

42.9

14.2

50

N/A

N/A

N/A

N/A

35.5

15.5

38.8

15.5

42.6

15.5

55

N/A

N/A

N/A

N/A

N/A

N/A

38.6

17.0

42.2

17.0

CUR122V40-1HP-0

40

32.0

14.0

35.4

14.2

39.4

14.3

43.3

14.4

47.8

14.6

45

32.2

15.2

35.5

15.3

39.3

15.5

43.1

15.6

47.5

15.7

50

N/A

N/A

N/A

N/A

39.2

16.8

42.9

16.9

47.1

17.0

55

N/A

N/A

N/A

N/A

N/A

N/A

42.7

18.4

46.7

18.5

Notes:
1

Output kW refers to the compressor duty.

2

Input kW refers to the compressor and fan input power only.