Network Display


The user will be able to view all modules connected to the AIRELAN.

By pressing

+

buttons, you can access each controller connected to the AIRELAN.


The display will show the unit number it is currently viewing at the top right-hand corner of the screen. (Examples




All the controllers connected to the AIRELAN network are identified using their own individual address. If duplicate
addresses are used the network will not work.


Addressing the Display Keypad


The address of the display keypad can be configured only after having connected the power supply, using the RJ11
connection cable.

To access the configuration mode, press the

+

+

buttons simultaneously and hold them for at least 5

seconds; the screen shown above will be displayed, with the cursor flashing in the top left corner.

To change the address of the display keypad (display address setting), press the

button once.


The cursor will move to the address field (



).

Use the

or

buttons to select the desired value, and press

again to confirm. The display below confirms

that the address has been successfully changed.


Note: If the field



” is set to

, the terminal will communicate with the pCO board usi

ng “point-to-point” protocol (not

pLAN). T

he field “I/O Board address: xx” will not be displayed, as this is not used with P2P protocol.