Confirm the FVS flow range - The Flow
Verification Sensor (FVS) will only function
within its operating range. Sensor model FV-
100-6V has an operating range of 30-300
ml/min (1-10 oz/min). If the pump’s output is
less than 30 ml/min (0.5 ml/sec), the sensor
will not detect chemical and a signal will not
be sent to the pump.

OPERATING

FLOW RANGE

(ml/min)

30-300

FV-100-6V

100-1000

FV-200-6V

200-2000

FV-300-6V

300-3000

FV-400-6V

500-5000

FV-500-6V

700-7000

FV-600-6V

SENSOR

MODEL

NUMBER

Install the FVS Flow Sensor - The Flow Verification Sensor (FVS) should
be installed on the outlet (discharge) side of the pump head valve. The
sensor includes a PVC tubing insert, located inside the sensor’s female
thread connection, that is designed to seal the sensor onto the pump head
inlet adapter. Thread the sensor onto the pump head until the tubing insert is
snug against the pump head inlet fitting - do not over-tighten.
Connect the red/white, black, and white wires from the sensor to the red,
black, and yellow wires located in the pump’s junction box. See page 7.

Contact Closure Alarm Output - A contact closure output (relay) is
provided with the FVS system. The relay can be configured for normally
open (factory default) or normally closed operation by properly positioning
the connector plug on the circuit board (see page 7).

C-1100V

Insert Tubing Seal

CAUTION

ADJUST WHILE RUNNING

DISCHARGE LINES MAY BE

UNDER HIGH PRESSURE. USE

CARE TO PROTECT YOURSELF

WHEN DISCONNECTING.

MAX

MIN

1

2

3

4

5

6

7

8

9

LOOSEN THE LOCK SCREW

TURN KNOB TO DESIRED SETTING

RE-TIGHTEN THE LOCK SCREW

Outlet Adapter

FVS Sensor

RUN

STANDBY

RUN

FIELD

DIGIT

MODE

PROGRAM

STAND-BY

PRIME

MINIMUM

MAXIMUM

INPUT MODES

1 - MANUAL

2 - 4-20mA

3 - 0-10VDC

4 - PULSE (Hz)

PROGRAM

RESET SERVICE

PRIME

DISPLAY

VARIABLE SPEED PUMP

% SPEED

MODE

VDC

SERVICE

ALARM

mA

Hz