PEP Filters HMF2 User Manual

Page 15

Advertising
background image


HMF2 Series Filter System

Operating & Maintenance Manual

PEP Filters

• 322 Rolling Hill Road • Mooresville, NC 28117 • 800-243-4583 •

www.pepfilters.com

15 of 19

Rev. 041204

Table 5a Electrical Requirements (3

φ, 60Hz)

PUMP

HP/KW

Voltage 3

φ

60 HZ

Full Load

Current (AMPS)

2 / 1.5

208, 230, 460, 575

7.5, 6.8, 3.4, 2.7

3 / 2.2

208, 230, 460, 575

10.6, 9.6, 4.8, 3.9

5 / 3.7

208, 230, 460, 575

16.7, 15.2, 7.6, 6.1

7.5 /5.6

208, 230, 460, 575

24.2, 22, 11, 9




Table 5b Electrical Requirements (3

φ, 50Hz)

PUMP

HP/KW

Voltage 3

φ∅

50 HZ

Full Load

Current (AMPS)

2 / 1.5

380, 415

3.4, 3.1

3 / 2.2

380, 415

5.2, 4.7

5 / 3.7

380, 415

8.0, 7.1




Table 6 Media Quantities for HMF2 Filters (non-code vessels)

HMF2 Filtration System

Size / Model

Fill Gravel

1 Pail = .5 ft

3

Unifill 475

Filter Media

(total quantity)

12

1 pail

1 pail

18

2 pails

2 pails

24

3 pails

4 pails

30

6 pails

6 pails

36

9 pails

9 pails

42

14 pails

12 pails

48

20 pails (or 10 bags)

16 pails (or 8 bags)

*Note: Please check your inspection report for exact amount. LOADING: Fill the filter 1/3 ~ 1/2 full

with water before loading the media. Load media in order described in “Media Loading” section of this

manual. Taking care to distribute the lower fill material around the under drain system, filling all

voids.