PEP Filters HMF2 User Manual

Page 9

Advertising
background image


HMF2 Series Filter System

Operating & Maintenance Manual

PEP Filters

• 322 Rolling Hill Road • Mooresville, NC 28117 • 800-243-4583 •

www.pepfilters.com

9 of 19

Rev. 041204

Seasonal Shutdown
The following services should be performed if the unit is shut down for a prolonged

time period.

1. Shut off all electrical power.
2. Close the shut-off valves in the filter inlet and outlet water lines. For units

using a backwash source other than the system, close the shut-off valve in

the line from that source.

3. Drain all external piping to and from the filter.
4. Open the manual vent valves and the drain line to the filter tank and piping.

After the water has drained, close the drain and vent.

5. On manual units only, rotate the valves manually by moving the linkage up

and down to ensure operation without obstruction.

6. Loosen the bolts that hold the filter access lid in place and remove the

inspection port cover. Lubricate the bolt and replace the port gasket if

necessary.

7. Inspect the over drain assembly and media pack. If the media is

contaminated, remove the foreign material and replace the media if

necessary. Install the filter access port and secure the bolts.


Maintenance Procedures
Pump Pre-Strainer
Warning
: Disconnect all electrical power prior to performing pump maintenance.

The filter pre-strainer basket on the pump inlet must be kept clean and free of

debris. Shut off the power, close the valves, open the air relief valve, remove bolts

and lid. Remove and clean the basket. Replace basket, lubricate O-ring, and tighten

bolts.


Backwashing
The filter media must be backwashed when the differential pressure is reaches

approximately 10 psig. Since the units with automatic controls perform this function

as necessary, a detailed backwash procedure is only provided with manual units.

The backwash cycle on automatic units can be manually initiated by pushing the

button on the control panel unit the valves change position. The valves will then be

automatically repositioned after two minutes. HMF2 filters should be back

washed once a week minimum.