HMF2 Series Filter System

Operating & Maintenance Manual

PEP Filters

• 322 Rolling Hill Road • Mooresville, NC 28117 • 800-243-4583 •

www.pepfilters.com

5 of 19

Rev. 041204

Note: The ¾” (20 mm) drain plug on HMF2 units is located on the tank bottom.

Actuator Requirements
PEP HMF2 filters utilize electric actuators to control the valve action between the

filtration and backwash cycles. The electric actuator is designed for 110 VAC control.

Air operated actuators are available as an option.

Wiring
HMF2 filters are supplied with a pump and automatic backwash controls and the

following system components: NEMA 4X control enclosure containing an on/off

disconnect switch, motor overload protection, transformer to provide 110 VAC

control voltage, adjustable backwash timer, 24 hour time clock, pressure differential

switch to initiate backwash, valve actuator to reposition valves for backwash, and
push button for manual backwash initiation. Units are provided with 460 VAC, 3

φ

close-coupled pump/motor assembly (110 VAC single phase panel if pump is not

furnished).
Units supplied with city or other source backwash are provided with a magnetic

motor starter. Units supplied with manual backwash are provided with no motor

control.
The following recommendations conform to the 2003 National Electric Code. Check

with local authorities for specific requirements.
Note: Refer to the pump/motor nameplate for horsepower and current draw.

Single Phase Manual Units

1. Install a separate power supply with circuit breaker protection between the

closest branch distribution panel and the pump motor. The full load current

for standard models is listed in Table 4.

2. Install an externally operated switch with fuse protection and door interlock in

plain sight of the filter and not more than 50ft (15m) away. The thermal

overload protection, if required, must be sized for full load amp draw listed on

the pump motor nameplate.

Three Phase Manual Units

1. Install a separate power supply line with circuit breaker protection between

the closest branch distribution panel and the pump motor. The full load