Whenever the level of electromagnetic interference is expected to be high, both the instruments and signal
cables should be placed as far away as possible from the source of interference.

In general, signal cables should be installed in bundles or channels / conduits, separate from other cables as
indicated in the table below:

Bus signals such as RS485

Data signals for PCs, printers etc.

shielded analog inputs

unshielded direct current (<= 60V)

shielded process signals (<= 25 V)

unshielded alternate current (<= 25V)

coaxial cables for CRT monitors

in common bundles or channels / conduits

direct current from 60 V to 400 V
(unshielded)

alternate current from 25V to 400 V
(unshielded)

in separated bundles or channels /
conduits, without minimum distance

direct and alternate current > 400 V
(unshielded)

Telephone lines

lines leading into EX-rated areas

in separated bundles or channels /
conduits, without minimum distance

Lightning protection


Cabling in areas with a risk of lightning requires a lightning protection. For cabling underground in between
buildings, we recommend the use of special fiber optic cables. If this is not possible, use copper cables that
are suitable for underground installation.

6.2 Guidelines for RS-485 wiring (HygroMet MP 3-wire)


See document E-DV04-RS485.01: RS485 Network Installation and Start-up Guidelines

6.3 Wiring color code


The HygroMet MP is supplied with 3m (9 ft) of PUR cable with tinned ends. Before connecting the
power, please make sure that there is no wiring error. Improper wiring may damage the HygroMet MP.

To facilitate maintenance of the HygroMet MP, keep the probe cable short. Do not replace the cable
supplied with the probe with a much longer cable. If a long length of cable is required, use an extension
cable with a maximum length of up to 330 feet (100 meters). When transmitting analog voltage signals
over a long distance, you should use separate wires for power ground and for each signal ground.