4.0 CALIBRATION

All relative humidity products are fully tested and calibrated prior to shipment in
accordance with the National Institute of Standards and Technology (NIST), the
highest quality standard available.

Once installed in the field, no calibration of the units is required. Instead, this
product suite features field-replaceable sensor modules that allow the end user
to replace the sensors on-site. This eliminates time consuming and costly factory
calibration, while reducing downtime during service intervals. Additionally, the
duct mount probe is easily accessed by taking off the front cover, removing the
sensor board assembly, and replacing the sensor module on the tip of the sensor
board. This further contributes to a more user-friendly, lower cost product line
that is focused on customer needs and ease of use.

4.1 Remove/Install the Sensor Tip
N

ote: Power Must be removed from the main PCBA prior to replacing the sensor

tip module. Failure to comply could possibly damage the sensor tip module

Wall Mount

Outdoor and Duct Mount

White

Retaining Clip