0 model 267 optional lcd display – Setra System 267MR User Manual

Page 10

Advertising
background image

with at least comparable accuracy to the 267 or 267MR transducer (<±1% FS).
With full range pressure applied to the high pressure port (reference port open
to atmosphere), the span may be adjusted by turning the SPAN adjustment
screw. (See Diagram 1 for location of SPAN adjustment.) Factory settings are:

Unidirectional Pressure Ranges

Bidirectional Pressure Ranges

Span Adjustment

Output

Span Adjustment

Output

5.0 VDC (±25 mV)

0-5 VDC

2.5 VDC (±25 mV)

0-5 VDC

10 VDC (±50 mV)

0-10 VDC

5 VDC (±50 mV)

0-10 VDC

Example 1: Unidirectional pressure range of 0 to 1” W.C. with 0 to 5 VDC out-
put

Apply 1.00” W.C., adjust span to 5 VDC (±25 mv)

Example 2: Bidirectional pressure range of ±5” W.C. with 0 to 5VDC output

Apply 5.00” W.C., adjust span to 5 VDC (±25 mV)

4.3 Current Output Zero Adjustment

While monitoring the current output , and with both pressure ports open to
atmosphere, the zero may be adjusted by turning the zero adjustment screw.
(See Diagram 3 for location of zero adjustment) Factory settings are:

Unidirectional Pressure Ranges

Bidirectional Pressure Ranges

Zero Adjustment

Output

Zero Adjustment

Output

4mA (0.08 mA)

4-20 mA

12 mA (0.08 mA)

4-20 mA

4.4 Current Output Span Adjustment

Span or full scale output adjustments should only be performed by using an
accurate pressure standard (electronic manometer, digital pressure gauge, etc.)
with at least comparable accuracy to the 267 or 267MR transducer (<±1% FS).
With full range pressure applied to the high pressure port (reference port open
to atmosphere), the span may be adjusted by turning the SPAN adjustment
screw. (See Diagram 1 for location of SPAN adjustment.) Factory settings are:

Unidirectional Pressure Ranges

Bidirectional Pressure Ranges

Span Adjustment

Output

Span Adjustment

Output

20mA (0.08 mA)

4-20 mA

20 mA (0.08 mA)

4-20 mA

Example 1: Unidirectional pressure range of 0 to 1” W.C. with 4 to 20 mA output

Apply 1.00” W.C., adjust span to 20 mA (±0.08mA)

Example 2: Bidirectional pressure range of 5” W.C. with 4 to 20 mA output

Apply 5.00” W.C., adjust span to 20 mA (±0.08 mA)

5.0 MODEL 267 OPTIONAL LCD DISPLAy

The Model 267 is available with an optional 3 1/2 digit LCD display. The LCD
display is adjusted at the factory prior to shipment. The LCD is connected to
the zero and span adjustment potentiometers. Therefore, adjustment of the
zero and span according to Section 4 adjusts the LCD display.