The dark square is the direction
the dipswitch should be set to.

DIRECT INTAKE VENT SYSTEM

This water heater may be converted to a direct-vent (sealed combustion) appliance by installing
an adapter (Part No. 9007669005 (TM-DV50)) which will bring all required combustible air from
outside the building. When installing the direct-vent conversion kit, please follow all instructions
included with the kit.

 The water heater must be installed in a location where the proper amount of combustible

air will be available to it at all times without obstructions.

 If used as a direct-vent appliance, the water heater requires a 5” combustible air supply

pipe. The intake pipe must be sealed airtight.

 Air supply pipe can be made of ABS, PVC, galvanized steel, corrugated aluminum,

corrugated stainless steel or Category III stainless steel.

 Change the dipswitch settings to the direct-vent system. (See diagram below)
 Sidewall venting is recommended for the direct-vent system.
 The manufacturer recommends running the exhaust vent and the intake pipe parallel.













Direct-Vent
Conversion Kit

Make sure power to the unit is
turned OFF before changing
the dipswitch settings.

O

N

TMP

1

TMP

2

TMP

3

MODE

DIRE

OUT

P-
A

L

A

R

M

MST

1 2 3 4 5 6 7 8

Lower Bank of Dipswitches

7-Seg LED

Lower bank of
dipswitches

Upper bank of
dipswitches

INTAKE

EXHAUST

DIRECT-VENT
CONVERSION KIT

LOUVER COVER PLATES