Takagi T-M50 User Manual

Page 4

Advertising
background image

- 4 -

TWO COMBUSTION SECTIONS WITHIN THE 910 (T-M50)

The water heater contains two combustion sections. The section that turns on first is whichever
section the water heater decides is the primary section. The moment at which the secondary
section fires will depend on the total flow rate and set temperature of the water heater:

Flow rate at which the secondary section fires

( GPM )

Set temperature of the 910 (T-M50)

(°F)

3.2 100-120
2.9 125,130
2.6 140
2.4 145,150
2.1 155-185

Example: If the set temperature is 120

ºF

:

*The section(s) in operation is indicated by the black square(s).

Right combustion section

*The primary and secondary section will reverse roles every 100 firing cycles or every 12 hours of unit operation.

Left combustion section

or

910 (T-M50)

910 (T-M50)

910 (T-M50)

910 (T-M50)

Depending on which side is the primary section

Total Flow < 0.5 GPM

(no section turns on)

0.5 GPM Total Flow < 3.2

GPM

(primary section fires only)

3.2 GPM < Total Flow

(both primary and

secondary sections fire)