Test mode – Timeguard 201.0.090 User Manual
Page 14
4
6. Test mode
The test mode serves to check the presence detection and the wiring
(Master-Slave parallel circuit operation).
6.1 Setting the test mode with DIP-Switch
Set DIP switch to «Test» (on all detectors in parallel circuit operation).
1. Start-up phase (30sec)
Both contacts are closed for 30sec. (LED 20s «on», 10s «off» )
2. Test mode
In case of movement (LED on), both contacts close.
In case of absence (LED off), both contacts open after 10sec.
NOTE: no brightness measurement, detector always in fully automatic mode.
The detector remains permanently in the test mode.
6.2 Setting the test mode with QuickSet plus
While setting the test mode with the service remote control QuickSet
plus, the detector jumps the start-up phase and changes directly into the
test mode.
Test mode ceases automatically after 10 minutes. The detector performs
a reset (see section 4.3).
●
●
●
●
●
●
●
●