8. Troubleshooting

Fault

Cause

Remedy

Lighting on after

the detector is

connected.

Both outputs are closed for 90

s after the detector has been

connected (test phase)

Wait for 90 s. The device then

responds immediately to changes in

brightness for 10 minutes.

Immediate re-

sponse to change

in brightness

The device is in service phase

(10 min.). This phase is used

to adjust the brightness setting

After the service phase, the re-

sponse to a change in brightness is

delayed to prevent sudden switching.

Lights never

switched on,

despite presence

of persons and

little daylight

1. Lux value too low.

2. Detection zone does not

cover the entire room. Vision

may be impaired.

1. Increase Lux value.

2. Change mounting location or

remove obstacles in detection range.

Lights flash

constantly

(«blinking»)

1. Halogen or incandescent

lamps triggered by ECO-IR.

2. Direct illumination from

fluorescent lamps too high.

1. Set Lux value to „on“ or replace in-

candescent lamps with FL/PL lamps.

2. check arrangement of detector

with regard to lamps.

Lights on con-

tinuously / de-

tector switches

without reason

1. Lux value too high.

2. Other movements have

been registered.

3. External contactor or relay

triggered

4. Several detectors connected

in parallel

1. Decrease Lux value.

2. Devices with instant heat emission

(e.g. heater), moving objects (curta-

ins, etc.) or domestic animals?

3. Fit inductive loads with spark

extinguishers (e.g. RC element).

4. Check Lux setting on detectors

Lights extinguish

despite presence

of persons

Minimum switch-off delay time

too low

Check recommended settings, incre-

ase switch-off delay time.

Detection zone

is smaller than

specified

1. Objects in visibility range

2. Detector positioned incor-

rectly

1. Remove obstacles, replace detector

2. Check detection range