When using suspended lighting, we recommend that you integrate the de-

tector directly in the lamps or provide a sufficient lateral clearance. When

using suspended lighting, note that the detection range may be shaded.

2.4 Switching contact «HVAC»

A potential free relay connects loads up to max. 100 W. The loads are only

connected if a person is detected, independent of the incident daylight. The

contact is closed if persons are detected.

2. Switch-off delay time «Light»

You can set the minimum duration to between 2 and 15 minutes. The ECO-

IR can extend this time setting (by max. 15 minutes) or reduce it to the

minimum value, depending on the frequency of movement (self-learning

effect). When set to 2 minutes, the switch-off delay is fixed.

2.6 Switch-off delay time «HVAC»

You can set the duration steplessly to between 10 and 60 minutes. Unlike the
«Light» switch-off delay time, the «HVAC» switch-off delay time is not adjusted
by the ECO-IR.

The switch-off delay times are restarted each time a movement is detected.