2 parameter description – TOHO ELECTRONICS TTM-P9 User Manual

Page 13

Advertising
background image

12

From reset mode

Hold the

▽ key and the PATT./STEP

key down simultaneously.

Set an alarm output lower limit.

Set an alarm output upper limit.

Press the PATT./STEP key.

PV



SV

PV



SV

Press the PATT./STEP key.


⑧ PID setting mode (The SET lamp lights.)

- This mode will set the PID constant (only during operation).

6.2 Parameter description

Program setting mode parameters

Character

Description

Initial value

Setting range

 □

Set a step

□ temperature

0

Setting range (K: 0 to 1200

°

C/J: 0 to 800

°

C/R: 0 to 1300

°

C

 □

Set a step

□ time

0.00

0 to 99 hours 59 minutes

Common parameter setting mode parameters

Character

Description

Initial value

Setting range



Set the PV correction zero
point

0

-199 to +199°C



Set the PV correction gain 1.00

0.50 to 2.00 times



Forward/reverse

switchover

2

1: Forward action (cooling)/2: reverse action (heating)

 

Sensor switchover

1

1: K thermocouple/2: J thermocouple/3: R thermocouple



SV limiter upper limit

1200

SLL + 50°C to setting range upper limit



SV limiter lower limit

0

0

°

C to SLH-50

°

C



Set the number of patterns 8

1 to 15 patterns



Select PV/SV start

PV

PV: PV start/SV: SV start



Set an SV start
temperature

0

Lower limit to upper limit of the temperature setting range

 

Proportional period

R (relay output): 20
S (SSR output): 2

1 to 120 seconds

 

Wait zone

0

0 to 100

°

C

 

Wait time

0.00

0 to 99 hours 59 minutes



Time signal/alarm output
type

00

(time signal)

0: Nil (time signal)
1: Deviation upper and lower limit
2: Deviation upper limit
3: Deviation lower limit
4: Deviation upper and lower limit

range

5: Absolute value upper and lower

limit

6: Absolute value upper limit
7: Absolute value lower limit
8: Absolute value upper and lower

limit range

0: No additional functions
1: Output

held

2: Standby

sequence

3: Output held + standby

sequence



Alarm output sensitivity

1

0 to 199°C



Time signal ON time

0.00

0 to 99 hours 59 minutes



Time signal OFF time

0.00

0 to 99 hours 59 minutes



Select an external
operation

OFF

ON: external operation /OFF: internal operation



Lock the key

OFF

ON/OFF