Wiring, 1 ttm-p4 series, 3 caution on wiring – TOHO ELECTRONICS TTM-P9 User Manual

Page 4: 2 ttm-p9 series

Advertising
background image

3

3. Wiring

3.1 TTM-P4 series

SSR drive

Control output

Power supply voltage
100 to 240VAC

±

10%

Relay contact

Operation signal

Output

Reserved

Reserved

Reserved

DI
(external input)

Time signal output/
alarm

Thermocouple input (K/J/R)

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

DI
(external input)

Operation

signal

Output

SSR drive

Control output

Power supply voltage
100 to 240VAC

±

10%

Relay contact

Time signal output/alarm

Thermocouple input (K/J/R)

3.3 Caution on wiring

Before wiring, be sure to turn off the power supply. Otherwise, you may get an electric
shock.

This equipment does not execute control operation for about 4 seconds after the power is
turned on. (Control output does not work. during the period)
Pay attention when you use this equipment for interlock circuit.
Confirm the wirings of the input terminal, power terminal, and optional terminal by reading
the label at the side of the equipment.

- Use crimping terminals matching to M3.5 screws. Also, when you wire to the central terminals, tighten the wire

directly.

- As for wire rods to be used for connecting this equipment with a thermocouple, use a specific compensating lead

wire or wire itself.

- When you use this equipment near the source of noise, use a shielded wire. Also, do not wire the input/output line

in the same duct or wire conduit.

- Leave the input/output signal line more than 50 cm away from the power and load lines.

3.2 TTM-P9 series

Warning

Caution