6.6 Precautions on RTU communications

6.6.1 Communications timing

Set a sufficient response delay to make sure that this product is switched over from transmission to
reception with regard to a high-level computer in using an RS-485.
See the figure in "5.1. Overview" and "5.7. Setting a response delay."

3.6.2 Interval between requests

In transmitting a series of "request messages" from a high-level computer, allow for an interval of
1msec or more or 3.5 character minutes, whichever the longer, from the reception of a "response
message" from this product to a next transmission.

6.6.3 Response conditions

If there is a time interval of 3.5 characters or more between data items constituting a "request
message," this product cannot recognize it as a "request message." It will therefore not return a
"response message." If, therefore, the "request message" contains an error, this product will not
return a "response message" (error reply) containing an ERR unless the above conditions are met.
Therefore transmit the necessary "request message" again if a "request message" is sent to the
high-level computer but the latter does not return a "response message" at the end of an appropriate
period.
The moment a period of 3.5 characters or more has elapsed, it clears all codes received before that.

6.6.4 Errors in address specification

This product will not respond to any "request message" that specifies an address other than that
specified for itself. If, therefore, the address portion of a "request message" is error-ridden, none of
the mobile units will return a "response message."
Therefore transmit the necessary "request message" again if a "request message" is sent to the
high-level computer but the latter does not return a "response message" at the end of an appropriate
period.

6.6.5 Number of digits in data and the decimal position

See "6.5. Description of RTU codes, g) Data portion."

6.6.6 Operation after receiving a store request message

This product starts to store data after correctly receiving a store request message from a high-level
computer.
This product only stores data different from the contents of the EEPROM (data that is changed).
The time (TW) required for storing data is within 6 seconds.
This product transmits a storage-complete reply after the data is stored.
This product will not guarantee that the data is stored if this product is turned off during a storage
operation. Do not turn off this product for 6 seconds after transmitting a store request message.

6.6.7 Operation after turning on the power

This product will not perform communications (no response) for about 4 seconds after it is turned
on. Allow for a delay until communications is started after this product is turned on.