10 parameter – TOHO ELECTRONICS TTM-00BT User Manual

Page 10

Advertising
background image

10

Parameter

a) Identifier

b) Name

c) R/W

d) Description and set range

e) Remark

Initial value (communication
numerical data)
TC, thermocouple;
Pt, resistance bulb

SV1

00000

Setting

R/W

r/w

R/W of the control settings
Thermocouple input:

Thermocouple K, 0.0 to 1300.0

°

C

Thermocouple J, 0.0 to 800.0

°

C

Resistance bulb input: PT100/JPT, -199.9 to 500.0

°

C

□CF

00000

Set a temperature unit

R/W

R/W of the

°

C/

°

F

°

C: 00000

°

F: 00001

Channel not specified

INP



TC: 00000

Pt: 00010

Set an input type

R/W

R/W of the input type settings
Thermocouple input models:

Thermocouple K: 00000

Thermocouple J: 00001

Resistance bulb input models:

Pt100: 00010

JPt: 00011

Neither the
thermocouple input nor
the resistance bulb
input can be changed.

PVG

00100

Set a PV correction gain

R/W

r/w

R/W of the PV correction gain setting
Set range: 0.50 to 2.00 times

Measurement
Gain correction

PVS

00000

Set a PV correction zero
point

R/W

r/w

R/W of the PV correction zero setting
Set range: -199 to 999

°

C/-199.9 to 999.9

°

C

Measurement
Zero correction

PDF

00001

Set an input filter

R/W

R/W of the input filter setting
Set range: 0 to 99 seconds

□DP

TC: 00000

Pt: 00001

Set a decimal point

R/W

R/W of the decimal point setting
No decimal point: 00000
Decimal point provided: 00001

□AT

00000

Start/release AT

R/W

R/W of the AT start/release
Start: 00001
Release: 00000

The W is not possible
during ON/OFF
control.