12 voltage input parameters, Unit common parameters – TOHO ELECTRONICS TTM-00BT User Manual

Page 12

Advertising
background image

12

Voltage input parameters

a) Identifier

b) Name

c) R/W

d) Description and set range

e) Remark

Initial value (communication
numerical data)
TC, thermocouple;
Pt, resistance bulb

DIF













00000

Set a voltage input function

R/W

R/W of the voltage input function setting

Numerical

data

Function type

When voltage is

applied

00000

None

00001

SV/SV2 function

SV2

00002

RUN/READY function

READY

00003

Auto/manual function

Manual

00004

Forward/reverse operation
function

Forward
operation

00005

Auto-tuning function

AT start

00006

Forward operation
(SV2)/reverse operation
(SV) function

Forward
operation (SV2)

SV2

00000

Setting 2

R/W

r/w

R/W of the control setting 2
Set range: SLL to SLH


Unit common parameters

a) Identifier

b) Name

c) R/W

d) Description and set range

e) Remark

Initial value (communication
numerical data)
TC, thermocouple;
Pt, resistance bulb

AWT

00000

Response delay setting

R/W

R/W of the response delay setting
Set range: 0 to 250mS

Channel not specified

MBK

00001

Memory bank reading

R/W

Replaces the specified memory bank with the current
memory bank.
00001 to 00008 (example: memory bank 1 is 00001)

No writing is possible
during AT.