Ethernet remote management ports, Daisy-chaining 10base-2 connections, Heat dissipation factors – ADC HiGain HMS-318 User Manual

Page 25: Figure 1-10.multishelf network ports, List, J24 j25, Thernet, Emote, Anagement, Orts

Advertising
background image

December 20, 2004

Chapter 1: Product Description

LTPH-UM-1261-01

1-13

Table 1-4. J27 – AUX RS-232 Management Port (DTE)

E

THERNET

R

EMOTE

M

ANAGEMENT

P

ORTS

The BNC connector J24 (labeled 10 BASE-2), see

Figure 1-10

, can be used to connect the management ports of up

to 32 shelves into an integrated network through a 10 BASE-2 (Thinnet) Ethernet LAN (IEEE.802.3). The rear-panel
RJ-45 connector J25 (labeled 10 BASE-T), see

Figure 1-10

, provides a 10 BASE-2 or a 10 BASE-T (Twisted-Pair)

Ethernet LAN (both IEEE.802.3 compatible).

Figure 1-10. Multishelf Network Ports

Daisy-Chaining 10BASE-2 Connections

10BASE-2 management ports of up to x number of shelves can be hubbed together by daisy-chaining together
using the included BNC-T connector. The last 10BASE-2 connection must be terminated with the included 50 ohm
BNC terminator.

H

EAT

D

ISSIPATION

F

ACTORS

The HMS-318 List 3 shelf is a 12-inch (30.48 cm) deep individual CO equipment shelf with open-faced mountings for
natural convection cooling. The maximum heat dissipation for open-faced, natural convection-cooled mountings is
limited to 134.7 Watts per square foot as defined in Section 4.1.4 of the NEBS standard for Physical Protection
(GR-63-CORE) for all equipment placed in a CO environment.

The heat dissipation footprint of an HMS-318 List 3 shelf is approximately 5.9 square feet. Therefore, the maximum
permissible heat dissipation per rack is 5.9 square feet x 134.7 Watts per square foot equals 790 Watts.

The maximum allowable heat dissipation for each telco-style equipment rack is:

• 790 watts for a 19-inch (48.3-cm) wide rack

Pin No.

Signal

Direction

1

Shield

2

Transmit Data (TD)

Out

3

Receive Data (RD)

In

6

Data Set Ready (DSR)

In

7

Ground (GND)

20

Data Terminal Ready (DTR)

Out

J24 J25

OS RS 2 32 P ORT

CO PA IR 2

AUX RS 23 2 DTE PO RT

S PA N PAIR 2

1

4-

1

261

R

1

1 0 BA SE -T

1 0 BA SE -2

1

2

3

4

5

CO PA IR 1

-4 8VA -4 8V B BAT RTN FGND

F US E F US E

P INS 3 & 4

MUS T B E BRI DGE D

15 A MA X 15 A MA X

2 5

2 5

2 5

1

1

1

2 6

2 6

2 6

S PA N PAIR 1

2 5

1

2 6

5 0

5 0

5 0

5 0