Gas piping recommendations:

A drip leg and a ground joint union must be installed in
the gas piping. A ground joint union is recommended by
the manifold/valve.

When required by local codes, a manual shutoff valve
may have to be installed outside of the unit.

Use pipe thread sealing compound resistant to propane
gas sparingly on male threads.

The gas supply should be a separate line and installed
in accordance with all safety codes listed on page 1.
After the gas connections have been completed, open
the main shutoff valve admitting normal gas pressure
to the mains. Check all joints for leaks with soapy solution
or other material suitable for the purpose.

Never use a flame to check for gas leaks. Explosion
causing injury or death may occur.

WARNING

The furnace and its individual manual shutoff valve must
be disconnected from the gas supply piping system
during any pressure testing of that system at test
pressures in excess of 1/2 PSIG (3.48kPa).

A 1/8" N.P.T. plugged tapping, accessible for test gauge
connections, must be installed immediately upstream
of the gas supply connection to the furnace.

Gas Connection
The gas supply line should be routed through the grommet
on the side of the unit.

The furnace must be isolated from the gas supply piping
system by closing the individual manual shutoff valve
during any pressure testing of gas supply piping system
at test pressures equal to or less than 1/2 psig or 14"
w.c. If the piping system is to be tested at pressures in
excess of 1/2 psig, the furnace and its individual shutoff
valve must be disconnected from the gas supply piping
system.

WARNING

Figure 4

2" Clearance Rear

24" Clearance

From Front

48" Overhead

Clearance

12" Clearance

(Both Sides)

To Unit Power Entry

Weatherproof

Disconnect Switch

To

Power

Supply

NEC Class 1 Wiring

Thermostat

NEC Class 2 Wiring

To Low Voltage Entry

NOTE: All outdoor wiring must be weatherproof.

Vent Cover

Power Entry

Low Voltage Entry

Gas Entry

15" Clearance
To Vent Cover

Typical Field Wiring