CHART 2

S8600 (NATURAL GAS AND LP GAS)

INTERMITTENT PILOT SYSTEM TROUBLESHOOTING

NO SPARK AT PILOT BURNER

Turn gas supply off.

Is voltage (24 Vac) across the 24 V terminals on “Call for heat”?

Is voltage (24 Vac) across the PV & MV/PV terminals on

“call for heat”?

NOTE: (FOR LP MODELS ONLY) Pilot valve will be de-energized

if module goes into lockout condition. Reset system by turning

electrical power off or by turning system controller to “OFF” or

down below “Call for heat”. Wait one minute then turn system on.

Turn off power supply.

Is ignition cable firmly plugged into module?

Is green ground wire firmly attached to mounting screw

and GND terminal on module?

Ensure ground strap is the closest metal to the igniter/sensor

rod (electrode) to prevent the spark from shorting out

to other metal parts (pilot screen, pilot shield, etc.).

Ignition cable must not touch metal surfaces or

current carrying wires.

Is there a 1/8” gap between ground strap and electrode?

Are the ceramic insulators surrounding the electrode

cracked or broken?

Replace pilot burner assembly or bus bar.

Replace ignition module.

Turn on gas supply.

turn on power supply.

Securely connect cable

and/or ground wire.

Carefully bend downward

top of ground strap

to achieve 1/8”

spark gap.

Replace ignition

module.

YES

NO

YES

YES

YES

YES

NO

NO

NO

NO