Horizontal Position

HORIZONTAL LEFT POSITION

Top Vent discharge

Figure 19

Disconnect pressure switch hose from barbed fitting on the pressure
switch assembly. Remove pressure switch assembly (1 screw) and cut
wire tie to free pressure switch wires. Reinstall pressure switch on the
other side of orifice plate and reconnect pressure switch hose.

Resecure pressure seitch wires: Either pull excess wires through the
blower compartment and secure using supplied wire tie, or coil excess
wire and secure to the gas manifold.

HORIZONTAL RIGHT POSITION

Top Vent Discharge

Figure 21

Remove make-up box assembly (2 screws) and cut wire tie to free make-
up box wires. Reinstall make-up box on other side of cabinet.

Resecure make-up box wires: Either pull excess wires through the blower
compartment and secure using supplied wire tie, or coil excess wire and
secure to the gas manifold.

HORIZONTAL RIGHT POSITION

Side Vent Discharge

Figure 22

HORIZONTAL LEFT POSITION

Side Vent Discharge

Figure 20

Disconnect pressure switch hose from barbed fitting on the pressure
switch assembly. Remove pressure switch assembly (1 screw) and cut
wire tie to free pressure switch wires. Reinstall pressure switch on the
other side of orifice plate and reconnect pressure switch hose.

Resecure pressure seitch wires: Either pull excess wires through the
blower compartment and secure using supplied wire tie, or coil excess
wire and secure to the gas manifold.