Allied Air Enterprises A80UH2V User Manual

Page 26

Advertising
background image

506471-01

Page 26 of 41

Issue 1034

4. Before connecting the thermostat, check to make sure

the wires will be long enough for servicing at a later
date. Make sure that thermostat wire is long enough to
facilitate future removal of blower for service.

5. Complete the wiring connections to the equipment. Use

the provided unit wiring diagram and the field wiring
diagram shown in Figure 41. Use 18 gauge wire or
larger that is suitable for Class II rating for thermostat
connections.

6. Electrically ground the unit according to local codes or,

in the absence of local codes, according to the current
National Electric Code (ANSI/NFPA No. 70). A green
ground wire is provided in the field make-up box.

NOTE: This furnace contains electronic components that
are polarity sensitive. Make sure that the furnace is wired
correctly and is properly grounded.

7. One line voltage “EAC” 1/4" spade terminal is provided

on the furnace integrated control. Any electronic air
cleaner or other accessory rated up to one amp can be
connected to this terminal with the neutral leg of the
circuit being connected to one of the provided neutral
terminals. See Figure 41 for control configuration. This
terminal is energized when the indoor blower is
operating.

8. One line voltage “HUM” 1/4" spade terminal is provided

on the furnace integrated control. Any humidifier rated
up to one amp can be connected to this terminal with
the neutral leg of the circuit being connected to one of
the provided neutral terminals. See Figure 41 for control
configuration. This terminal is energized in the heating
mode whenever the combustion air inducer is operating.

9. One 24V “H” terminal is provided on the furnace

inte-grated control terminal block. Any humidifier rated
up to 0.5 amp can be connected to this terminal with
the ground leg of the circuit being connected to either
ground or the “C” terminal. See Figure 41 for control
configuration.

10. Install the room thermostat according to the instructions

provided with the thermostat. If the furnace is being
matched with a heat pump, refer to the instruction
packaged with the dual fuel thermostat.

Indoor Blower Speeds
1. When the thermostat is set to “FAN ON,” the indoor

blower will run continuously at approximately 38% of
the second stage cooling speed when there is no cooling
or heating demand.

2. When this unit is running in the heating mode, the indoor

blower will run on the heating speed designated by the
positions of DIP switches 11 and 12.

3. When there is a cooling demand, the indoor blower will

run on the cooling speed designated by the positions of
DIP switches 5 and 6.

Generator Use - Voltage Requirements
The following requirements must be kept in mind when
specifying a generator for use with this equipment:

The furnace requires 120 volts ± 10% (Range: 108 volts
to 132 volts).

The furnace operates at 60 Hz ± 5% (Range: 57 Hz to
63 Hz).

The furnace integrated control requires both polarity and
proper ground. Both polarity and proper grounding
should be checked before attempting to operate the
furnace on either permanent or temporary power.

Generator should have a wave form distortion of less
than 5% RHO.

Electrical Wiring

Risk of electrical shock. Disconnect electrical power at
the circuit breaker or service panel before making
electrical connections. Failure to disconnect power
supplies can result in property damage, personal injury,
or death.

WARNING

The furnace must be grounded and wired in accordance
with local codes or, in the absence of local codes, with the
National Electrical Code ANSI/NFPA No. 70 (latest edition)
and/or CSA C22.1 Electrical Code (latest edition) if an
external electrical source is utilized.

Table 10

Advertising
This manual is related to the following products: