Dryer Exhaust Requirements . . .

Never install flexible duct in concealed spaces, such as
a wall or ceiling.

Exhaust System Materials

Exhaust duct must be four inches (10.2 cm) in diameter
having no obstructions. Rigid metal duct is
recommended. Non-combustible semi-rigid flexible
metal duct is acceptable. Do not use plastic pipe or
flexible plastic pipe, because it contributes to poor
drying performance and collects lint, which can lead to
a fire hazard.

DO NOT use sheet metal screws on exhaust pipe joints
or other fastening means which extend into the duct
that could catch lint and reduce the efficiency of the
exhaust system. Secure all joints with duct tape.

Make-Up Air Requirements

For proper operation it is important that you locate the
dryer in an area that has an ample amount of make-up
air to replace the amount exhausted by the dryer.

Energy efficient homes with low air infiltration rates
should be equipped with an air exchanger that can
accommodate on demand make-up air needs in the
home. These devices can be obtained through your
building contractor or building material suppliers.

A clothes dryer produces combustible lint.
To reduce the risk of fire and combustion
gas accumulation the dryer MUST be
exhausted to the outdoors.

W116

This gas appliance contains or produces a
chemical or chemicals which can cause
death or serious illness and which are
known to the State of California to cause
cancer, birth defects, or other reproductive
harm. To reduce the risk from substances in
the fuel or from fuel combustion, make sure
this appliance is installed, operated, and
maintained according to the instructions in
this manual.

W115

To reduce the risk of fire and the
accumulation of combustion gases, DO NOT
exhaust dryer air into a window well, gas
vent, chimney or enclosed, unventilated
area, such as an attic, wall, ceiling, crawl
space under a building or concealed space
of a building.

W045

To reduce the risk of fire, DO NOT use
plastic pipe or flexible plastic pipe to
exhaust the dryer.

W041

WARNING

DO

D314IE0B

DON'T

D315IE0A