Modbus alarm registers – HP Power Distribution Unit Management Module User Manual

Page 45

Advertising
background image

HP PDR Management Module web interface 45

Register Name

Panel Breaker Count Format Units

2745 Breaker

212.42

2 1-42 840 UNIT16 0.01

WS

ModBus alarm registers

Use function code 02h to read the discrete input contacts (alarm status).
PDR ModBus alarm registers (1-bit) include:

Register Name

Count

1001

Input AC Over Voltage

1

1002

Input AC Under Voltage

1

1003

Input Under Over Frequency

1

1004

Output AC Over Voltage

1

1005

Output AC Under Voltage

1

1006

Output Under Over Frequency

1

1007

Remote Emergency Power Off

1

1008 Building

Alarm

4

1

1009 Building

Alarm

3

1

1010 Building

Alarm

2

1

1011 Building

Alarm

1

1

1012 Output

Overload

1

1013

Output Current Over 100Percent

1

1014 Eeprom

Fault

1

1015

Internal Communication Failure

1

1016

Input Phase Rotation Error

1

1017

Emergency Shutdown Command

1

1018

Level 2 Overload Phase A

1

1019

Level 2 Overload Phase B

1

1020

Level 2 Overload Phase C

1

1021

Level 3 Overload Phase A

1

1022

Level 3 Overload Phase B

1

1023

Level 3 Overload Phase C

1

1024

Level 4 Overload Phase A

1

1025

Level 4 Overload Phase B

1

1026

Level 4 Overload Phase C

1

1027 Transformer

Overtemperature

1

1028 Modem

Failed

1

1029 Configuration

Error

1

1030 Summary

Notice

1

1031 Summary

Alarm

1

1032 Inverter

Phase

Rotation

1