Overview – APC InfraStruXure Power Supply User Manual

Page 25

Advertising
background image

InfraStruXure Site Planning, Installation, Start-Up

17

Connect User Contact Inputs and Output
Relays to the User Connection Plate

Overview

Make contact closure connections (NO

or NC) at the user connection plate to

monitor dry contacts. You can make

eight connections—four contact inputs

and four output relays.

The figure at the right shows the location

of the user connection plate on the roof

of the PDU enclosure.

You can make connections from inside

the enclosure, or you can remove the

user connection plate and make your

connections.

Remove the plate using a Phillips or

standard screw driver to loosen the two

captive screws. Use the knockout in the

plate to route cables to and from the user

connections on the plate. If you remove

the plate, make sure that you do not

disturb the existing connections.

Output relay specifications

Nominal switching capacity:

1A at 30VDC

Maximum switching power:

30W

Maximum switching voltage:

60VDC

Maximum switching current:

2ADC

Maximum carrying current:

2ADC

Surge ratings:

2kV per Bellcore TA-NWT-001089
1.5kV per FCC part 68

1

2

3

4

AT

S E

N

AT

S 0

AT

S

1

AT

S 2

EPO

Contact

– +

EPO 24V

AC/DC

Contact Inputs

Contact Outputs

USER INTERFACE

© 2001 APC

MADE IN USA