3-Phase Stacking (Three FX Series Inverter/Chargers Only)

A 3-phase stacked system with only three FXs must be set up as described here:

• Turn off all AC output and AC input breakers before powering up FXs.

• Plug the top FX into Port 01 of the HUB, the 2nd FX into Port 02, and the 3rd FX into Port 03.

• Change the HUB jumper for 3-phase stacking (refer to the HUB manual).

• Go to the fi rst MATE stacking menu (Stack Phase) press the <PORT> soft key until Port 01 appears.

• Set the Stack Phase of the Port 01 FX to 3ph Master by pressing the <INC> soft key. The Master FX is

considered phase A.

• Press the <PORT> soft key and verify P02 (2nd FX) displays.

• Press the <INC> soft key fi ve times to set the Stack Phase to 3ph Slave. The P02 FX is now set as

phase B, producing 400VAC between itself and the Master (P01).

• Press the <PORT> soft key again and verify P03 (3rd FX) is displayed.

• Push the <INC> soft key fi ve times to set the Stack Phase to 3ph Slave. This FX (P03) is now set as

phase C, producing 400VAC between itself and the master (P01) and also 400VAC between itself and

the FX on phase B.

NOTE: The AC input to a 3-phase system must be a 3-phase source (generator or grid).

PRESS <INC> UNTIL 141,
THEN PRESS ENTER

ADV----------------------------

choose a device:

FX CC DC MATE

ADV/FX/PAGE 1-------------

choose category:

ADV INV CHGR PG2

ADV/FX/PAGE2--------------

choose category:

PG1 GRID GEN PG3

ADV/FX/PAGE3---------------

choose category:

PG2 AUX STACK PG4

ADV/FX/STACK -------P01

stack 1-2ph Master

phase

DOWN INC DEC PORT

ADV/FX/STACK--------P01

stack 3ph Master

DOWN INC DEC PORT

MAIN--------------------------
8:25:04A

SUM STATUS SETUP ADV

ADV/SETTINGS/WARNING

changes made could adversely
aff ect system performance

ADV/PASSWORD---------------

enter the password

132

ENTER INC DEC EXIT

PRESS INC FOUR TIMES