8

To choose your AC input source in the ac transfer

control screen, press or .

Press to view the next screen.

By using

and

, the ac1/grid menu

sets the maximum current the FX will allow to be

drawn from the grid by either AC loads and/or

the batteries (during recharging). When this limit

is exceeded, an AC input limit warning appears

and the FX will reduce the almount of charging so

that the total current draw does not exceed the

maximum setting (between 2.5AAC and 30.0AAC).

Press to view the next INPUT screen.

The ac2/gen limit screen sets the maximum

current the FX will allow to be drawn from a

generator by either AC loads or the batteries

(during recharging). When this limit is exceeded,

the FX will reduce the amount of charging cur-

rent so the total current draw does not exceed

the maximum setting (between 1.0AAC and 30.0

AAC) to avoid damage to the generator. Press the

to view the fi nal INPUT screen.

Pressing

returns you to the SETUP/FX/

SEARCH screen.

Pressing returns the user to the choose

category screen.

Pressing

returns to the MAIN Menu.

.

SETUP/FX/INPUT----------P00
ac transfer

Gen

control

DOWN GRID GEN PORT

SETUP/FX/INPUT----------P00
ac1/grid

24.5 aac

limit

DOWN INC DEC PORT

SETUP/FX/INPUT----------P00
ac2/gen

30.0 aac

limit

DOWN INC DEC PORT

SETUP/FX/INPUT----------------
input

setup

completed

TOP SETUP MAIN

GRID

GEN

DOWN

INC

DEC

DOWN

DOWN

TOP

SETUP

MAIN