Operating and installation instructions

TEMPTROL

®

5.3 Installation instructions concerning actuators

(Connection of valve with thermal controller)

Construction
- Set point of the thermal controller/detector, turn to maximum. Hold the set point indicator

with the other hand.

- Connect the actuator (pos. 50.16) (ca. 100 Nm) through the connecting nut to the valve

(pos. 11). (Attention: The actuator must not turn whilst connecting, because the capillary
tube (pos. 50.15) will be damaged!).

Dismantling
- Loosen the connecting nut of the actuator (pos. 50.16). (Attention: The actuator must not

turn, because the capillary tube (pos. 50.15) will be damaged!).

-

ATTENTION !
- It is not permitted to mantle / dismantle actuators with valves operating and in

service conditions (temperature and pressure) (refer to item 10.0).

- If a temperature sensor is placed in a vessel with flammable or explosive media,

a sensor pocket have be provided.

-

ATTENTION !
- The actuator (pos. 50.16) seals the valve interior only metallic;

not extra gasket is allowed!

- No sharp bending or unscrewing of capillary tubes is allowed; passes control

medium on hot surfaces it may ignite. Combustion danger!

-

ATTENTION !
- When loosening the actuator, dangerous media can escape

(hot condensate, steam)