Rev. 0040702000 1011

Page 27

Operating and installation instructions

TEMPTROL

®

5.2.1 Thermo controller with 2 temperature sensors
- The first temperature controller (pos. 50.1a) (a bar sensor for liquids or a spiral sensor for

air) measures the external temperature (regulating variable).

- The second temperature controller (pos. 50.1b) (a bar sensor) measures the external

temperature (command variable). It should be mounted outside wall - north side away
form the sun, 2m above ground and protected from wind.

- The influence of the external temperature on the controlled temperature is possible due to

the difference in volume between the first sensor (regulating variable) and the second
sensor (command variable).

- The set point indicator has a trend scale with a middle mark (refer to setting diagrams in

the data sheet).

5.2.2 Selection of temperature sensor- Location
- The temperature sensor (pos. 50.1) must be completely immersed.

Care should be taken to assure adequate circulation.

- At low flow rates, we recommend installing the temperature sensor (pos. 50.1) horizontally

(for example in boilers at 2/3 height).

- The control thermometer should be installed near the location from temperature sensor.
- In pipelines, a threaded coupler must be welded into the pipe and the temperature sensor

mounted against the flow direction.

- When installing the temperature sensor (pos. 50.1) directly, be sure the connection is free

of leaks (gasket is included).

- Room temperature sensors should not be exposed to interference such as drafts, sunlight

and other sources of heat.