4 manual control device, Operating and installation instructions temptrol – ARI Armaturen TEMPTROL 774 EN User Manual

Page 11

Advertising
background image

Rev. 0040702000 1011

Page 29

Operating and installation instructions

TEMPTROL

®

5.4 Manual control device

- The manual control device is installed between the valve (pos. 11) and the actuator

(pos. 50.16) of the thermal control valve (Fig. 5).

- Note, that here also the sealing is only metallic, no extra gasket!
- The connecting nut (pos. 60.14) is fastened with about 100 Nm to the valve (pos. 11), the

actuator (pos. 50.16) with about 50 Nm to the manual control device.

In the following, a setting example is shown for a closing valve:
- Turn the adjusting ring (pos. 60.5) clockwise till the valve (pos. 11) is closed (mechanical

endpoint). The upper securing ring (pos. 60.3) is put in line with the notch of the pin
(pos. 60.11).

- Now turn the adjusting ring (pos. 60.5) anti-clockwise, till the valve (pos. 11) is full open

(max. flow). The bottom securing ring (pos. 60.3) is put in line with the notch of the
indicator pin (pos. 60.11). In the system you can then see the lift over the open and closed
position between the securing rings (pos. 60.3).

- Note, that when working the adjusting ring (pos. 60.5) must be in the opening position of

the valve; closed valve can’t be opened through the thermal controller!

Pos.

Designation

11

Bonnet (valve)

50.16

Actuator

50.17

Connecting nut (actuator)

60.3

Securing ring

60.5

Adjusting ring

60.11

Pin

60.14

Connecting nut

Fig. 5