The DeviceNet Resolver operates as a “Group

2 only slave” device. It operates as an input only

device on the DeviceNet network. All device

configurations are accomplished by using any

DeviceNet software configuration tool.

The DeviceNet Resolver is capable of

communicating at all three DeviceNet baud rates,

125K, 250K, and 500K. The node address can

be set to any address, 0 - 63. There are several

parameters: scale factor, counting direction, and

8 programmable setpoint that are configured or

modified by the user through the Parameter Object.

(See section 4.0: DeviceNet Resolver Object

Model).

2.1: LED Operation

The DeviceNet Resolver is equipped with a Network

Status LED. The network Status LED operates as

follows:

Solid Green = Allocated by Master

Flashing Green = Passed Duplicate MAC ID Test

and is awaiting to be allocated by Master

Solid Red = Fatal error. Requires user intervention.

Check for duplicate MAC ID or baud rate

communication rate setting.

2.2: I/O Messaging

The DeviceNet Resolver supports Bit-Strobe

Message Connection as well as a Polled I/O

Message connection. The DeviceNet Resolver does

not support Cyclic I/O or Change-of-State Message

Connections.

Bit Strobe Message

A bit strobed message connection is a very fast

method by which a master sends one bit (Bit Strobe

Command) out on the network and receives up to

8 bytes of data (Bit Strobe Response) from each

slave device that supports a Bit Strobe Message

Connection. The DeviceNet Resolver disregards the

command message. No user-defined configuration

is required.

Polled I/O Message

A polled message connection is used for devices

that have inputs and outputs. It can also be used for

“Input Only” devices. The master sends out a Polled

Command to each individual device and the device

responds with an 8 byte Polled Response. The

Polled message connection is not the most efficient

message connection to use for “Input Only” devices

because there is a Command message sent to and

a Response message sent from each device. This

creates a lot of unnecessary network traffic.

2.3: Data Format

The setpoint status is supplied in the first 8 bits

of the I/O message. One bit for each setpoint,

“0 = off” and “1 = on”. The next 16 bits will provide

the scaled resolver position information

(4095

maximum). And finally, the next 16 bits will provide

the RPM data

(1024 maximum). The entire I/O

message is 40 bits long. You will need to reserve 40

bits in your controller I/O image table.

Chapter 2: DeviceNet Information

Setpoint Data

Position Data

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Position Data

RPM Data

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

RPM Data

Not Used

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

Not Used

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63