AMETEK 1990 DN DeviceNet Resolver Interface Module User Manual

Page 6

Advertising
background image

6

1080 N. Crooks Road • Clawson, MI 48017 • 800.635.0289 • 248.435.0700 • Fax 248.435.8120 • www.AMETEKAPT.com

3.3.3: Position Offset

The indicated position of the resolver can be

changed to synchronize or “zero” the resolver to the

machine it is attached to. The resolver position can

be changed by moving the resolver at the desired

position and writing the desired indicated position to

attribute 1 of the Position Object. All setpoints will be

based on this offset position. A valid position value

can range between, and include, zero and the scale

factor. (i.e. 0 < position < scale factor).

3.3.4: Setpoints

As indicated the DeviceNet Resolver has 8

programmable setpoints. Each setpoint is

individually programmed through the Parameter

Object. Each setpoint has an “On Position” value

and an “Off Position” value. All setpoint defaults are

set to 0.

Each setpoint has only one “On” and

one “Off” per revolution.

NOTE: The setpoints can be changed after the

scale factor has been established. The setpoints

cannot be configured outside the scale factor range.

Setpoint 1 “On” Position

Set

Parameter Instance 5 Attribute ID 1 Desired On Position Value

Setpoint 1 “Off” Position

Set

Parameter Instance 6 Attribute ID 1 Desired Off Position Value

Setpoint 2 “On” Position

Set

Parameter Instance 7 Attribute ID 1 Desired On Position Value

Setpoint 2 “Off” Position

Set

Parameter Instance 8 Attribute ID 1 Desired Off Position Value

Setpoint 3 “On” Position

Set

Parameter Instance 9 Attribute ID 1 Desired On Position Value

Setpoint 3 “Off” Position

Set

Parameter Instance 10 Attribute ID 1 Desired Off Position Value

Setpoint 4 “On” Position

Set

Parameter Instance 11 Attribute ID 1 Desired On Position Value

Setpoint 4 “Off” Position

Set

Parameter Instance 12 Attribute ID 1 Desired Off Position Value

Setpoint 5 “On” Position

Set

Parameter Instance 13 Attribute ID 1 Desired On Position Value

Setpoint 5 “Off” Position

Set

Parameter Instance 14 Attribute ID 1 Desired Off Position Value

Setpoint 6 “On” Position

Set

Parameter Instance 15 Attribute ID 1 Desired On Position Value

Setpoint 6 “Off” Position

Set

Parameter Instance 16 Attribute ID 1 Desired Off Position Value

Setpoint 7 “On” Position

Set

Parameter Instance 17 Attribute ID 1 Desired On Position Value

Setpoint 7 “Off” Position

Set

Parameter Instance 18 Attribute ID 1 Desired Off Position Value

Setpoint 8 “On” Position

Set

Parameter Instance 19 Attribute ID 1 Desired On Position Value

Setpoint 8 “Off” Position

Set

Parameter Instance 20 Attribute ID 1 Desired Off Position Value

Advertising