DRC

Valve Controller

Open Loop Double Solenoid Control (DRC2-Vxx)

The DRC can drive a double solenoid valve with a
joystick or potentiometer of

10kΩ.

If enable switch is not used, set channel 1 to be Mode
1, channel 2 to be Mode 3.

If enable switch is used, set channel 1 to be Mode 2,
channel 2 to be Mode 3.

The minimum and maximum input parameters for the
two channels should not be overlap.

Set the dither and output settings according to the
valve specifications.

Schematic

FUSE

+V Power Input
9 - 32VDC

+V = Enabled

PWR J1-1

DRC2

Electronic Valve

Controller

Enable J1-3

GND J1-2

-10V Ref. Out J4-1

+10VDC @ 20mA

0 to 10VDC

+10V Ref. Out J4-3

Ch. 1 I/P J5-1

Sig GND J4-2

J5-2

V

D

C

I/

P

m

A

I/

P

Supply Voltage

4-20mA

Ch. 2 I/P J5-3

Prop. PWM (Sourcing)

Sig GND J2-2

Ch. 1 Out J2-1

Ch. 2 Out J2-3

Prop. PWM (Sourcing)

0 to -10VDC

Example Settings

Input / Output Diagram

-10V

(Ch. #2)

600mA

5mA

600mA

5mA

Center (0V)

Ch.

#2

Current

Ch.

#1

Current

10V

(Ch. #1)

Command

Input

-0.2V

(Ch. #2)

0.2V

(Ch. #1)

Parameter

Value

C1 Mode

2 IN1 USE ENBL

C1 Min input

0.2 V

C1 Max input

10.0 V

C1 Min output

5 mA

C1 Max output

600 mA

C1 Ramp up

1 S

C1 Ramp down

1 S

C2 Mode

3 IN1 FOLLOWER

C2 Min input

-0.2 V

C2 Max input

-10.0 V

C2 Min output

5 mA

C2 Max output

600 mA

C2 Ramp up

0 S (NOT USED)

C2 Ramp down

0 S (NOT USED)

Dither frequency

150 Hz.