Table 9:

CLARY OutPost

TM

BATTERIES*

Estimated Runtime

(Per set @ 77°F / 25°C)

(New Batteries, fully

charged)

Unit

Weight

Overall Dimensions

Per Battery Inches (cm.)

Clary

Part. No.*

Volts/

A-hrs.

300

Watts

500

Watts

700

Watts

875

Watts

Lbs.

(Kg.)

Length

L

Width

W

Height

H

OP72C

(Set of

6

Batteries)

12

VDC/

41 AH

6.3

Hrs.**

3.8

Hrs.**

2.5

Hrs.**

1.8

Hrs.**

29

(13.2)

7.68

(19.6)

5.15

(13.1)

7.9

(20.1)

Clary

Part. No.*

Volts/

A-hrs.

300

Watts

700

Watts

1050

Watts

1400
Watts

OP96C

(Set of 8

Batteries)

12

VDC/

41 AH

8.5

Hrs.**

3.5

Hrs.**

1.5

Hrs.**

1.0

Hrs.**

*OP72C battery sets include six (6) batteries per set. Wired in series, each set provides 72 VDC.

*OP96C battery sets include eight (8) batteries per set. Wired in series, each set provides 96

VDC.

** Actual times may vary, runtimes are dependent on many factors.

Lower/Higher AH capacity batteries, allowing less or more runtime, are available on special order.

Contact factory for more information.

Communications, Controls & Diagnostics

Optional TCIP/Ethernet available, contact factory for more information.

Front Panel controls: Power ON, Cold (DC) Start, Alarm Silence, Battery Test, Bypass Circuit

Breaker, and DC/Battery Circuit Breaker.

Options

Battery Tray to hold three (3) OP72C batteries is 19” wide for use in 170 type cabinets and

mounts on standard RETMA rails.

Swing-out Battery Box, mounts on right rail inside back door of 170 type cabinets. Box is designed

to hold tree (3) OP72C batteries