35

Table 12: LIST OF RULES

#

Rule

Description

Parameters

00

Relay Off

Turns Relay OFF.

None

01

On_Bat

Activates when UPS is on
Battery Mode.

None

02

Low_Bat_1

Activates when batteries reach
user settable capacity level.

Set battery capacity in %
Limits 0% - 100%, Resolution 1%

03

Bat_Timer_1

Activates after user settable
time when UPS is in Battery
mode.

Set Timer in HH:MM:SS
Limits 00:00:00 – 18:12:15, Resolution 1 Second

04

Alarms_1

Activates when Alarm
conditions occur.

See Alarm/Fault Table
Allows you to choose which alarms you want to
activate this condition. You may choose all or just
some.

05

Faults_1

Activates when Fault
conditions occur.

See Alarm/Fault Table

06

Low_Bat_2

Additional Low_Bat condition.
Functions same as Low_Bat_1.

Set battery capacity in %
Limits 0% - 100%, Resolution 1%

07

Bat_Timer_2

Additional Bat_Timer
condition. Functions same as
Bat_Timer_1.

Set Timer in HH:MM:SS
Limits 00:00:00 – 18:12:15, Resolution 1 Second

08

Alarms_2

Additional Alarm condition.
Functions same as Alarms_1.

See Alarm/Fault Table

09

Faults_2

Additional Fault condition.
Functions same as Faults_1.

See Alarm/Fault Table

10

Low_Bat_3

Additional Low_Bat condition.
Functions same as Low_Bat_1.

Set battery capacity in %
Limits 0% - 100%, Resolution 1%

11

Bat_Timer_3

Additional Bat_Timer
condition. Functions same as
Bat_Timer_1.

Set Timer in HH:MM:SS
Limits 00:00:00 – 18:12:15, Resolution 1 Second

12

Alarms_3

Additional Alarm condition.
Functions same as Alarms_1.

See Alarm/Fault Table

13

Faults_3

Additional Fault condition.
Functions same as Faults_1.

See Alarm/Fault Table

14

Fan_Ctrl_1

Activates at Temperature
levels set by user.

Set Hi/Lo limits. Choose from internal sensor or
external(Aux) sensor. There is a minimum Five°C
differential limit between the HI and Low limts.
Limits 0˚C - 125˚C, Resolution 1˚C

15

Fan_Ctrl_2

Additional Fan Control
condition.

Set Hi/Lo limits. Choose from internal sensor or
external(Aux) sensor. There is a minimum Five°C
differential limit between the HI and Low limts.
Limits 0˚C - 125˚C, Resolution 1˚C