INDICATION

LIKELY REASON

REMEDY

no power to valve power supply off

check connection of power supply

power supply problem

disconnect GFM transducer from
power supply; remove the shorting
condition or check polarities; fuse
resets automatically

pc board defective

check power supply for appropriate
output

no response to
set point

inadequate gas pressure

return to factory for replacement

cable or connector malfunction apply appropriate gas pressure

cable or connector malfunction

check cables and all connections or
replace

set point is too low
(<2% of full scale)

re adjust set point

valve adjustment wrong

re adjust valve

pc board defective

return to factory for replacement

(f)

TROUBLESHOOTING

f.1 Common

Conditions

Your Solenoid Valve Driver Module was thoroughly checked at numerous quality
control points during and after manufacturing and assembly operations.

It was carefully packed to prevent damage during shipment. Should you feel that
the instrument is not functioning properly please check for the following com-
mon conditions first:

Are all cables connected correctly?

Is the power supply correctly selected according to requirements?

Were the connector pinouts matched properly? When interchanging with other
manufacturers' equipment, cables and connectors must be carefully wired for
correct pin configurations.

f.2 Troubleshooting

Guide