Caution – Samlex America SAM-3000-12 User Manual

Page 24

Advertising
background image

22 | SAMLEX AMERICA INC.

SAMLEX AMERICA INC. | 23

down. Red LED "Overload" will be ON and Green LED "Power" will also be ON. The unit will
latch in shutdown condition. To reset, switch OFF the ON/OFF switch, wait for 3 minutes and
switch ON again.

Ground fault protection will also operate if the neutral and ground of the ac output of the

inverter are connected (bonded) intentionally like in Service entrance / Load center for ac
distribution wiring.

!

caution!

connecting to utility ac distribution wiring with neutral to Ground connection (bond) is not permit-
ted. in ac utility distribution wiring, the neutral conductor is connected (bonded) to the equipment
Grounding conductor at the Load center / Service entrance. Both these conductors are then bonded
to the earth Ground (Ground rod). thus, if the output of the inverter is connected to the utility ac
distribution wiring, it will see a neutral to Ground connection and the inverter will trip due to
activation of the Ground fault protection circuit as explained above.

failure to Start Some Devices on Load

Some high capacitance loads like Compact Fluorescent Lamp (CFL) or Switched Mode
Power Supply (SMPS) will shut down the inverter under overload condition if the inverter
is switched ON with these loads in ON condition. However, if these loads are switched
OFF first and switched ON only after around 10 sec after the inverter is switched ON (as
already recommended under switching ON procedure), the inverter may not shut down.
Hence, do not switch ON the inverter with such loads in ON condition.

monitoring of operational Status & protections

Normal / abnormal behavior can be monitored by observing Green LED (6, Power), Yellow
LED (5, Input Fault), Red LED (7, Fault) and Buzzer. Details are given in Table 6.1 below:

table 6.1 protections and monitoring

operating

condition/

protection

threshold/

reason

Green

LeD (6,

power)

yeLLoW

LeD (5,

input

fault)

reD

LeD (7,

fault)

Buzzer

remedy/reset

Normal

-

ON

OFF

OFF

OFF

-

Low DC Input

Alarm

10.8V ± 0.3V

ON

OFF

OFF

ON

Check battery voltage and

input voltage drop.

Auto reset when voltage

> 10.5 V ± 0.3V.

No Output

due to Low DC

Input Voltage

shutdown

10.5V ± 0.3V

OFF*

ON

OFF

ON

Check battery voltage and

input voltage drop.

Auto reset when voltage

rises to >11.5V.

No output due

to High DC

Input Voltage

Shut Down

15.5 ± 0.2V

OFF*

ON

OFF

OFF

Check charger voltage.

Auto reset when voltage

< 15.5V.

SECTION 6 |

Protections Monitoring

& Trouble-Shooting

11002-SAM-1000-1500-2000-3000-12-0814.indd 24

14-08-12 9:59 AM