CPI PDU User Manual Rev. 10.0.

June 28, 2010

29

• Descriptions of the fields are listed below.

PDU MAC: Contains the assigned MAC address for the PDU’s network interface
hardware. This value cannot be changed.

PDU IP: Contains the assigned IP address for the PDU in the form of
xxx.xxx.xxx.xxx, where xxx is a number from 1 to 254. The factory-assigned IP
address is 192.168.123.123.

Netmask: Contains the network masking bits (sub-net mask) for the PDU in the
form of xxx.xxx.xxx.xxx, where xxx is usually 255 or 0 to designate a bit pattern
that masks in the network address portion of the IP address. These values
depend on the network class of the assigned IP address. The factory-assigned
netmask is 255.255.255.0.

Gateway: Contains the IP address of the network’s gateway PDU in the form of
xxx.xxx.xxx.xxx, where xxx is a number from 1 to 254. The factory-assigned
gateway is 192.168.123.1.

DHCP Checkbox: Check to use dynamic IP address assigned by a DHCP server
instead of the static IP assigned in the PDU IP address field.

Hosts Checkbox: Check to indicate that only the Hosts listed in the SNMP Host
IP Address fields can access the PDU via SNMP. When unchecked, any host
can access the PDU via SNMP.

WEB Checkbox: Check to allow access to the PDU using a web browser. This
box should always be checked.

SWU Checkbox: Check to allow software updates.

SNMP Host1 IP Address: The PDU will send current, temperature and humidity
alarms to this IP Address as SNMP traps. Leave 0.0.0.0 to disable. Not required
when SEMA is used to monitor the PDU.

SNMP Host2 IP Address: The PDU will send over current, temperature and
humidity alarms to this IP Address as SNMP traps. Leave 0.0.0.0 to disable. Not
required when SEMA is used to monitor the PDU.

SNMP Host3 IP Address: The PDU will send over current, temperature and
humidity alarms to this IP Address as SNMP traps. Leave 0.0.0.0 to disable. Not
required when SEMA is used to monitor the PDU.

PDU Name: Name assigned to this PDU, the maximum number of characters
that can be entered is less than 32.

Min Temperature: Set the low temperature threshold (in degrees) that when
reached the PDU will send an alarm notification via SNMP trap over the network.
The range of values that should be entered is 0 through 199 degrees Fahrenheit
or -17 through 100 degrees Celsius when the Celsius box is checked. If this
variable is set to 0°F the notification is disabled.