P ow erS cope U ser M anual R ev. X 1

A ugust 1, 2009

13


These are the configuration variables for the PowerScope:


Log Interval: Time interval (in seconds) that the PowerScope will send updated
metrics to SEMA over network. If this variable is set to a value of less than 10
the logging is disabled. Maximum value that can be entered is 64,000.

Alarm Interval: Time interval (in seconds) that the PowerScope will send
notification to SEMA over network when an alarm condition arises. If this
variable is set to a value of less than 10 the alarm notification is disabled.
Maximum value that can be entered is 64,000.

Log Difference: Absolute value difference (in Amps) that the PowerScope must
detect in the change of consumption before it will send updated metrics to SEMA
over network. If this variable is set to 0 the difference logging is disabled.
Maximum value that can be entered is 640.00.

PDU Connection Port: This is the TCP/IP port number that the PowerScope uses
to listen for communications from SEMA. This value is normally set to 2001 and
should not be changed unless it is done system wide with the SEMA. Maximum
value that can be entered is 64,000.

SEMA Connection Port: This is the TCP/IP port number that the SEMA uses to
listen for communications from a PowerScope. This value is normally set to
2002 and should not be changed unless it is done system wide with the SEMA.
Maximum value that can be entered is 64,000.

PDU Broadcast Port: This is the TCP/IP port number that the PowerScope uses
to listen for broadcast communications from SEMA. This value is normally set to
2003 and should not be changed unless it is done system wide with the SEMA.
Maximum value that can be entered is 64,000.

SEMA Broadcast Port: This is the TCP/IP port number that the SEMA uses to
listen for broadcast communications from a PowerScope. This value is normally
set to 2004 and should not be changed unless it is done system wide with the
SEMA. Maximum value that can be entered is 64,000.

SEMA IP Address: Contains the assigned IP address for SEMA in the form of
xxx.xxx.xxx.xxx, where xxx is a number from 1 to 254.

PDU IP Address: Contains the assigned IP address for the PowerScope in the
form of xxx.xxx.xxx.xxx, where xxx is a number from 1 to 254.

PDU MAC Address: Contains the assigned MAC address for the PowerScope’s
network interface hardware. This value cannot be changed.

Subnet Mask: Contains the network masking bits for the PowerScope in the form
of xxx.xxx.xxx.xxx, where xxx is usually 255 or 0 to designate a bit pattern that
masks in the network address portion of the IP address. These values depend
on the network class of the assigned IP address.