Chatsworth Products PowerScope In-Line Meter User Manual

Page 22

Advertising
background image

P ow erS cope U ser M anual R ev. X 1

A ugust 1, 2009

20

Specifications

Dimensions: 17”W x 1.75”H x 9”D (Rack-mount, 19”EIA x 1 RMU)

Weights: up to 13 lbs for the dual input unit with 3ft cable length.

Altitude:
• Operating: 0 to 10,000 ft (0 to 3048 m)
• Non-operating: 0 to 30,000 ft (0 to 9144 m)


Audible Noise: Less than 60 db LpA (Sound pressure level at bystander position)
The above noise level is not for office environment. It is for dedicated Datacenter
environment.

Heat Dissipation: 10 BTU/hr maximum.

Shock and Vibration:
• Operating: 5 to 500 Hz, 0.5 g (0.1 octave/min)
• Non-operating: 5 to 100 Hz, 1 g (0.1 octave/min); 100 to 500 Hz, 1.5g (0.2

octave/min); 500 to 1000 Hz, 1.5 g (0.2 octave/min)

Electrical
• Grounding: Chassis grounded.
• Voltage: 110 or 208V AC
• Current: 20 or 30 Amps per input
• Line Frequency: Single phase 50 or 60 Hz.
• Output Power Capacity: 20 or 30 Amps per output
• Configurable Power: 20 or 30 Amps per output
• Nominal Output Voltage: 110 or 208V AC (same as input)
• Output Voltage distortion: same as input
• Output Frequency: 50 or 60 Hz (same as input)
• Waveform type: same as input

Temperature:
• Operating

:

32° (0°C) to 104° (40°C)

• Storage: -4° (-20°C) to 140° (60°C)

Humidity:
• Operating: Non-condensing, 10 to 90 percent.
• Storage: Non-condensing, 5 to 95 percent.


Local Connection:
• RJ11connector: Environmental probe connection
• RJ45 connector: Serial connection

Remote Connection:
• Network: 10/100/1000 RJ45
• Network Protocol: TCP/IP