Digital energy gt series, 2 start-up, 3 use: normal operation – Chatsworth Products GT Series UPS (3-10kVA) User Manual

Page 12

Advertising
background image

OPM_GTU_TWR_1K0_3K0_XUS_V015

11

DE GT Series: User manual rev date 8-11-04

Digital Energy GT Series

g


3.2 Start-up

3.2.1 Start-up, utility power available

1 Push the ‘I/TEST’-button (1) and hold

for 3 seconds until a short beep is

heard. The bypass LED will shortly light

up. When the LED ‘On Line’ lights up,

the UPS is running in ‘ON LINE’ mode.

2 The equipment connected to the UPS

can now be switched on.

3.2.2 Start-up, utility power not available

(cold start or battery start)

1 Push the ‘I/TEST’-button (1) and hold

for 3 seconds until a short beep is

heard. The battery LED and LED ‘On

Battery’ will light up. The UPS operates

in ‘ON BATTERY’ mode”: it discharges

the batteries.



3.3 Use:

Normal

Operation

3.3.1 Normal operation conditions:

 the utility power supply is present and within allowable tolerances,

 the load does not exceed the nominal rating of the UPS and

 the operating temperature is below alarm level

 the UPS is on,


3.3.2 Normal operation indications:

 LEDs ‘Line’, ‘On Line’ and the Load LED

are

on

 One or more LEDs on the level bar are on

 the buzzer is silent




3.3.3 UPS

self-test

Press the ‘I/TEST’-button (1) when the

UPS is in ‘ON LINE’ mode. The UPS will

shift to ‘ON BATTERY’ mode and

automatically perform a self-test for about

10 seconds (as in fig. 3.5). The self-test

function will check the condition of the

battery. After self-test is finished and test is

O.K, the UPS will return to ‘ON LINE’

mode.

Fig. 3.2 On Line mode

Fig. 3.3 On Battery mode

Fig. 3.4 Normal operation

Fig. 3.5 UPS self test