Digital energy gt series, 7 - troubleshooting – Chatsworth Products GT Series UPS (3-10kVA) User Manual

Page 19

Advertising
background image

OPM_GTU_TWR_1K0_3K0_XUS_V015

18

DE GT Series: User manual rev date 8-11-04

Digital Energy GT Series

g

Whenever a malfunction occurs, first check external factors (e.g. connections, temperature,

humidity or load) to determine whether the problem is caused by the unit itself or by its

environment. Subsequently check the thermal circuit breaker: it may be tripped. If so: reset it

and be sure that the UPS is not overloaded.

The following chart is a simple troubleshooting checklist only. If the suggested solution does

not succeed, or if the information is insufficient to solve the problem, please contact your dealer.

PROBLEM

POSSIBLE CAUSE

SOLUTION

UPS overload

Reduce load, reset breaker

Input Circuit Breaker tripped

System failure

Contact your dealer or consult

www.gedigitalenergy.com

UPS will not switch on

Line cord not connected

Connect line cord

Dead wall socket outlet, or

mains voltage out of limits

Contact qualified electrician

Tripped input circuit breaker

Check whether UPS is not

overloaded, reset breaker

Battery voltage too low

Allow UPS to recharge the battery

Batteries

not

connected

Contact your dealer or consult

www.gedigitalenergy.com

UPS has no output

UPS over-temperature

Allow UPS to cool down

Utility failure, battery depleted Wait until utility power returns

Input breaker tripped

See above

LED ‘Fault’ lights up, buzzer

sounds continuously

Internal UPS failure

Contact your dealer or consult

www.gedigitalenergy.com

LED ‘Fault’ flashes

Wiring fault (L-N reversed)

Have site wiring checked by

qualified electrician

LED ‘Battery low’ lights up,

buzzer beeps 2x/sec.

Battery is close to being

exhausted during utility failure

The UPS output will be lost soon.

Shut down the load in an orderly

manner

LED ‘Replace battery’ lights up,

buzzer sounds continuously

Battery test just after a utility

failure (‘false alarm’)

Allow the UPS to recharge the

battery for approx. 8 hours, then

repeat the battery test

Battery is close to being worn

out

Allow the UPS to recharge the

battery for approx. 8 hours, then

perform battery test. If the alarm

persists, consider battery

replacement

LED ‘Overload’ lights up,

buzzer sounds continuously

UPS is overloaded

Reduce load, e.g. by unplugging

non-critical load

Buzzer sounds continuously:

over-temperature

Ambient temp. too high, or

ventilation blocked

Reduce ambient temperature,

enhance ventilation

Fan failure

Have the fan replaced

UPS cannot be linked to

computer

Communication cable

defective

Check cable

Transmitting

rate

fault

Adjust transmitting rate

Communication port fault

Check COM1/COM2 configuration

of the computer

7 - Troubleshooting