Digital energy gt series, 8 - specifications – Chatsworth Products GT Series UPS (3-10kVA) User Manual

Page 20

Advertising
background image

OPM_GTU_TWR_1K0_3K0_XUS_V015

19

DE GT Series: User manual rev date 8-11-04

Digital Energy GT Series

g

GT Model

1000T UL

1500T UL 2000T UL

3000T UL

Capacity

1kVA/800W

1.5kVA/ 1200 W

2kVA/1600W

3kVA/2400W

Rated Voltage

100V, 110V, 120V

Voltage Range

80V~138V (full load); 65V~80V (70% load)

Frequency

50Hz / 60Hz (± 4.8 Hz)

Input

Power Factor

0.97

Voltage

100V, 110V, 120V

Frequency 50Hz

/

60Hz

Voltage Regulation

± 2%

Frequency Accuracy

± 0.05 Hz

Wave Form

pure sine wave

Transient Response

± 8% (10%

90% linear load)

THD (linear load)

3%

3%

4%

THD (computer load)

6%

Overload Capacity

105%~125% for 3mins; 125%~150% for 30secs; >150% for 1sec

Crest Factor

3:1

Output

Efficiency (AC-AC)

 87%

Outlet

Receptacles NEMA

TYPE

Battery Voltage

36V

72V

72V

Battery Type (Lead acid)

12V/7Ah 12V/7Ah 12V/9Ah

Back-up Time
(Typical)

5mins

Battery

Recharge Time

4~6 hours after complete discharge to recover 90%

Transfer
Time

Transfer Time

zero

LED Status

On-line / Bypass / On-battery / Overload / Battery Low / Fault

Battery Replace / Battery Level / Load Level

LED

Alarm buzzer
DB9 RS232/dry

contact

Interface

SNMP Slot

internal

Noise (At 1 Meter)

40dB(A)

42dB(A)

45dB(A)

Operating
Temperature

0~40°C (32~104°F)

Environment

Humidity 0%~90%

(non-condensing)

Safety UL/cUL

EMC

FCC Class A (2, 3kVA) /B (1kVA)

CISPR PUB 22 Class B; TUV/EMC; CE (1kVA)

CISPR PUB 22 Class A (2, 3kVA)

Safety
Approval

Lightning

IEEE 62.41 Category A

Battery Start

yes

Extended Battery
Bank

yes (optional for longer runtime)

Others

Long Time Model

yes (optional)

Dimensions
(W

×D×H)

140x366x242 mm

5.5x14.4x9.5 inch

140x425x373mm

5.5x16.7x14.7 inch

Appearance

Weight

15 kg

33 lbs

30 kg

66 lbs

30 kg

66 lbs

8 - Specifications

Advertising