Appendix D. Setting Up RF401-to-

CR206(X) Communications

Certain CR206(X) settings must match the RF401 settings for communications

between the datalogger and radio to be successful. The factory default settings

of these devices may not match.

D.1 CR206(X) Setup Information

1. Access the Deployment panel in DevConfig (see FIGURE D-1).

FIGURE D-1. CR206 Setup Main Menu

2. PakBus Address: Must match the PakBus Address in LoggerNet.

3. RF Protocol: Select PakBus Aware if the RF401s and RF430s in your

network are set to PakBus Aware or PakBus Node. The Transparent

setting must be used if your network includes CR205 dataloggers or

RF400 radios. If Transparent is used, all dataloggers and radios in the

network must be set to Transparent.

4. Hop Sequence: Must match all of the RF401 and RF430 radios and other

CR206(X) dataloggers in the network.

5. Network: must match the Network Address setting for all RF401 or

RF430 radios in the Network. All other CR206(X) dataloggers must also

have the same Network setting.