Heater Running but Not Heating

Icebreaker Analog Controls - 1/20/04

START

Is the air being discharged

out of the top of the heater 9-12

degrees cooler than the

outside air?

START

Is the air being discharged

out of the top of the heater 9-12

degrees cooler than the

outside air?

Is the pool pump

timer set to allow extended

operation of
the heater?

Is the pool pump

timer set to allow extended

operation of
the heater?

Yes

Is the heater

performing

adequately?

Is the heater

performing

adequately?

Problem

Solved.

Problem

Solved.

No

Yes

No

Yes

Call AquaCal for

Assistance:

800-786-7751.

Call AquaCal for

Assistance:

800-786-7751.

No

Yes

No

Problem

Solved.

Problem

Solved.

Did defrost cycle terminate

(defrost light off), and is discharge

air now 9-12 degrees cooler than

the outside air?

Did defrost cycle terminate

(defrost light off), and is discharge

air now 9-12 degrees cooler than

the outside air?

Is the defrost light on and

compressor operating (no fan)?

Is the defrost light on and

compressor operating (no fan)?

Yes

No

Extend the pool pump's hours

of operation, to accommodate

additional heater run time

required due to cool/cold

weather conditions.

Extend the pool pump's hours

of operation, to accommodate

additional heater run time

required due to cool/cold

weather conditions.

The defrost light illuminated, with the

compressor operating, indicates the

heater is in defrost. Heater will

remain in defrost until evaporator is

free of ice or for a maximum

of 10-minutes.

The defrost light illuminated, with the

compressor operating, indicates the

heater is in defrost. Heater will

remain in defrost until evaporator is

free of ice or for a maximum

of 10-minutes.