3 battery backup mode, 4 charging mode, 0 operation – Alpha Technologies FLEXNET POWER MPS48-7M User Manual

Page 23

Advertising
background image

23

021-511-B4-002, Rev. B

5.0 Operation

5.3 Battery Backup Mode

In the event of an AC power outage, the MPS48-7M switches to battery backup mode to
power the load. The green status LED begins to blink, indicating the load is being powered
from the battery string. The MPS48-7M runs in battery backup mode until AC power is
restored, or until the battery string reach a low-voltage shutdown level of 42V. On resumption
of AC power, the MPS48-7M recharges the batteries at a maximum current of 1.8A.

5.4 Charging

Mode

Under normal conditions, a fl oat charge maintains the batteries at 100% capacity. In the
event of line failure, battery charging resumes automatically when primary power is restored.
Charging continues until one of the following occurs:

Battery has reached 100% of capacity.

Another power failure occurs requiring battery support. Charging ceases until primary
power is restored.

Additional power is required by the load, in which case power is diverted from the battery
charger and sent to the load. When demand for additional power ceases, normal battery
charging resumes.

Fig. 5-2, Battery Capacity Versus Temperature

Runtime (hours) vs Temperature

Typical Recharge time vs Load

Load

-40°C

0°C

25°C

40°C

20Watts

12.5

13.4

16.0

20

13 hr

40Watts

6.0

6.3

7.6

10

25 hr

50Watts

3.3

4.1

5.7

7.2

50 hr

Table 5-2, Battery Runtime and Recharge Times

0

20

40

60

80

100

120

-40°F
(-40°C)

-20°F
(-29°C)

0°F
(-18°C)

20°F
(-7°C)

40°F
(4°C)

60°F
(16°C)

80°F
(27°C)

100°F
(38°C)

Ambient Air Temperature

B

a

tt

er

y

C

ap

aci

ty

(%

)

without heater mat

with heater mat

Battery Capacity (%) vs. Temperature

*This chart is an approximation of the effectiveness of a heater verse no heater.